Background Image
Table of Contents Table of Contents
Previous Page  163 / 218 Next Page
Information
Show Menu
Previous Page 163 / 218 Next Page
Page Background

CIRCUIT TECHNIQUE

Figure 57

Pos. 1

: with the introduction of anAND valve, the two previous valves can be powered directly from the network.

The

a0

valve is actuated and there is always a signal on the AND valve, the Start outlet is only active if the

I.C.

valve is actuated. The cycle is a single cycle.

Pos. 2

: the same connectionas the example inPos. 1with the introduction of twomonostable3/2-wayNC valves,

which allow the separation of the Start Cycle

I.C.

and End cycle

F.C.

, commands.

This condition requires the introduction of a double pneumatically operated bistable 3/2-way valve tomemorize

the signals from the two control valves.

Cycle start command

In a machine/plant, the sequence may be executed with both a

single

or semi-automatic cycle in addition to a

continuous

or

automatic

cycle. In both cases it is necessary for the start command to be given by a Start Cycle

(

I.C.

) (InizioCiclo) valve. In a

single

cycle the commandmust be repeated each time the sequence restarts. In this

case the valve that generates the start signal is a monostable valve. In a

continuous

cycle the command is only

given at the start. In this case the valve that generates the start signal is a bistable valve.

In the continuous cycle the Start Cycle (

I.C.

) valve in the actuated positionmust be connected in series with the

last signal to have confirmed the correct position of the actuators at the end of the sequence. When this valve is

deactivated (i.e. no passage between inlet 1 and outlet 2), there is no continuous cycle and the start signal cannot

restart the sequence.

Figure 56

Pos. 1

:

as the flow chart indicates, Phase 4 is the final phase, during this Phase

a0

is the last limit switch to be

activated.

Pos. 2

:

the outlet of valve

a0

, i.e. the last signal to have confirmed the correct position of the actuators at the

end of the sequence, feeds the

I.C.

valve, which in turn permits the passage of the signal although only if it is in

C.C.

(Continuous Cycle) position. In the position shown below the valve is closed indicating it is in the

F.C.

(End

of Cycle) position. In the case of amonostable

I.C.

valve, the cyclewould be a single cycle andwould need to be

operated at each sequence end.

Pos. 3

:

contrary to the previous situation, the

I.C.

valve is fed by the compressed air. It is only possible to generate

the Start commandwhen both the

I.C.

valve and the limit switch

a0

are operated.

1

2

3

+

_

A

+

_

B

cycle

3

1 2

4 1 2 3

a1

b0

b1

I.C.

a0

I.C.

I.C.

a0

a0

Fig. 56

The Start function can be achieved with manual monostable valves and manual bistable valves. The choice

remains with the designer of the circuit to adopt themost adequate solution for the application involved.

Start

Start

I.C.

I.C.

F.C.

a0

a0

1

2

Fig. 57

5

161

CAMOZZI

>

CIRCUIT TECHNIQUE